Share

Motor Duty Cycle

Last updated: 5 May 2025
42 Views

S1 : Continuous running duty

The duty type S1 can be defined as operation at a constant load maintained for sufficient time to allow the machine to reach thermal equilibrium.

For a motor suitable to this duty type, the rating at which the machine may be operated for an unlimited period is specified.

This class of rating corresponds to the duty type whose appropriate abbreviation is S1.

 

__________________________________________________________________________________________________________________________
 

S2 : Short time duty

The duty type S2 can be defined as operation at constant load for a given time, less than that required to reach thermal equilibrium, followed by a time de-energized and at rest of sufficient duration to re-establish the equilibrium between the machine temperature and that of the coolant temperature.

For a motor suitable to this duty type, the rating at which the machine, starting at ambient temperature, may be operated for a limited period is specified. This class of rating corresponds to the duty type whose appropriate abbreviation is S2

 

 

__________________________________________________________________________________________________________________________
 

S3 : Intermittent periodic duty

The duty type S3 is defined as a sequence of identical duty cycles, each including a time of operation at constant load and a time de-energized and at rest. The contribution to the temperaturerise given by the starting phase is negligible

A complete designation provides the abbreviation of the duty type followed by the indication of the cyclic duration factor (S3 30%).

 

Figure 4 : Intermittent periodic duty: Duty type S3

ΔTc Operation time at constant load

ΔT0 Time de-energized and at rest

Cyclic duration factor = ΔTc/T

 

 

__________________________________________________________________________________________________________________________
 

S4 : Intermittent periodic duty with starting

The duty type S4 is defined as a sequence of identical duty cycles, each cycle including a significant starting time, a time of operation at constant load and a time de-energized and at a rest.

A complete designation provides the abbreviation of the duty type followed by the indication of the cyclic duration factor, by the moment of inertia of the motor JM and by the moment of inertia of the load JL, both referred to the motor shaft (S4 20% JM = 0.15 kg m2 JL = 0.7 kg m2)

Figure 5 Intermittent periodic duty with starting: Duty type S4

ΔT* Starting/accelerating time

ΔTc Operation time at constant load

ΔT0 Time de-energized and at rest

Cyclic duration factor = (ΔT* + ΔTc)/ T
 

 __________________________________________________________________________________________________________________________
 

S5 : Intermittent periodic duty with electric braking

The duty type S5 is defined as a sequence of identical duty cycles, each cycle consisting of a starting time, a time of operation at constant load, a time of electric braking and a time de-energized and at a rest.

 A complete designation refers to the duty type and gives the same type of indication of the previous case.

Figure 6 Intermittent periodic duty with electric braking: Duty type S5

ΔT* Starting/accelerating time

ΔTc Operation time at constant load

ΔTf Time of electric braking

ΔT0 Time de-energized and at rest 

Cyclic duration factor = (ΔT* + ΔTc + ΔTf)/ T

 

________________________________________________________________________________________________________________________
 

S6 : Continuous operation periodic duty

The duty type S6 is defined as a sequence of identical duty cycles, each cycle consisting of a time of operation at constant load and a time of operation at no-load. There is no time de-energized and at rest.

 

A complete designation provides the abbreviation of the duty type followed by the indication of the cyclic duration factor (S6 30%).

Figure 7 Continuous-operation periodic duty: Duty type S6

ΔT* Operation time at constant load

ΔT0 Operation time at no load

Cyclic duration factor = ΔTc/ΔT0

 

 

 

________________________________________________________________________________________________________________________
 


Related Content
Motor Inertia and Motor Starting Time
Total GD2 is the sum of load GD2 + Motor GD2 + Coupling GD2 , Torque Speed Curve
Insulation Class and Temp Rise Class
NSULATION CLASS The IEC 60085 specifies that an Insulation system permanently submitted to its Insulation Class temperature has a life expectancy of 20 000h. TEMPERATURE RISE CLASS The temperature rise class is the maximum allowed difference between the measured temperature, after temperature stabilisation, of one of the active generator components (stator or rotor copper) and the cooling fluid temperature (e.g. ambient air temperature for instance, at 40°C).
เว็บไซต์นี้มีการใช้งานคุกกี้ เพื่อเพิ่มประสิทธิภาพและประสบการณ์ที่ดีในการใช้งานเว็บไซต์ของท่าน ท่านสามารถอ่านรายละเอียดเพิ่มเติมได้ที่ นโยบายความเป็นส่วนตัว and นโยบายคุกกี้
Compare product
0/4
Remove all
Compare
Powered By MakeWebEasy Logo MakeWebEasy